OpenPLC_v3 Heap-Based Buffer Overflow in Modbus Master getData()
Get instant alerts when new vulnerabilities affect OpenPLC_v3 - before attackers find them.
OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.
Our own answer: ranges merged, affected separated from platform-only, with confidence and review flags.
No remediation guidance has been written for this CVE yet. What the record does show:
Patch and advisory references
SSVC signals action urgency (what to patch first), separate from CVSS which measures severity.
Get alerted