CVE-2022-38371

HIGH
7.5
CVSS Score
Published: October 11, 2022 at 12:00 AM UTC
Updated: June 17, 2026 at 04:56 AM UTC
46 products affected across 1 vendorNucleus Source CodeApogee Pxc Modular FirmwareTalon Tc Compact Firmware

Using APOGEE MBC (PPC) (BACnet) by Siemens?

Get instant alerts when new vulnerabilities affect APOGEE MBC (PPC) (BACnet) - before attackers find them.

Real-time alertsTrack your software stackFree plan available
Severity
HIGH7.5
Exploit prediction
EPSS 2%
SSVC
No known exploit

Description

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), Desigo PXC00-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC00-U (All versions >= V2.3 < V6.30.37), Desigo PXC001-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC100-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC12-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC128-U (All versions >= V2.3 < V6.30.37), Desigo PXC200-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC36.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC50-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC64-U (All versions >= V2.3 < V6.30.37), Desigo PXM20-E (All versions >= V2.3 < V6.30.37), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (All versions including affected FTP server), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.

Affected

Our own answer: ranges merged, affected separated from platform-only, with confidence and review flags.

All versions
siemens-apogee-modular-building-controller (same device)
All versions
siemens-apogee-modular-equiment-controller (same device)
All versions
siemens-apogee-pxc-compact (same device)
All versions
siemens-apogee-pxc-modular (same device)
v ≤ 2.3
siemens-desigo-pxc00-e-d (same device)
v ≤ 2.3
siemens-desigo-pxc00-u (same device)
v ≤ 2.3
siemens-desigo-pxc001-e-d (same device)
v ≤ 2.3
siemens-desigo-pxc100-e-d (same device)
v ≤ 2.3
siemens-desigo-pxc12-e-d (same device)
v ≤ 2.3
siemens-desigo-pxc128-u (same device)

Remediation

No guide yet

No remediation guidance has been written for this CVE yet. What the record does show:

SSVC — Action Prioritization

SSVCNo known exploitAutomatablePartial impact

SSVC signals action urgency (what to patch first), separate from CVSS which measures severity.

CVSS

7.5HIGHsiemens
Vector?

Quick Info

StatusMODIFIED
CWE
CWE-400CWE-401