Get instant alerts when new vulnerabilities affect N/A - before attackers find them.
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Our own answer: ranges merged, affected separated from platform-only, with confidence and review flags.
No remediation guidance has been written for this CVE yet, and no fixed version or vendor advisory is recorded against it.
SSVC signals action urgency (what to patch first), separate from CVSS which measures severity.
Get alerted
Track the products you run and VulnTracker tells you when a new CVE affects them — with what is known about fixing it, and nothing about the rest.